Master MPS
Power Range: 10 - 200 kVA
Power Range: 10 - 200 kVA
FEATURES
- Smart Online UPS
- Output Power Factor 90%
- Efficiency Control System (ECS)
- Robust and Reliable
- Galvanic Isolation
- Parallelable up to 8 Units
- High Overload Capacity
- Extensive Parallel Configurations
| MODELS | MPM 10BAT | MPM 15BAT | MPM 20BAT | MPM 30 | MPM 40 | MPM 60 | MPM 80 | MPM 100 |
|---|---|---|---|---|---|---|---|---|
| INPUT | Â | |||||||
| Rated Voltage [V] | 380 / 400 / 415 three-phase + N | |||||||
| Voltage tolerance [V] | 400 ±20% - 25% @ full load1 | |||||||
| Frequency [Hz] | 45-65 | |||||||
| Soft start | 0 - 100% in 120 sec. (selectable) | |||||||
| Permitted frequency tolerance | ±2% (selectable from ±1% to ±5% from front panel) | |||||||
| Standard equipment provided | Back Feed protection; separable bypass line | |||||||
| BYPASS | Â | |||||||
| Rated Voltage [V] | 220 / 230 / 240 single-phase + N | |||||||
| Rated frequency [Hz] | 50 or 60 (selectable) | |||||||
| OUTPUT | Â | |||||||
| Nominal power [kVA] | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 |
| Active power [kW] | 9 | 13,5 | 18 | 27 | 36 | 54 | 72 | 90 |
| Number of phases | 1 | |||||||
| Rated voltage [V] | 220 / 230 / 240 single-phase + N (selectable) | |||||||
| Static stability | ±1% | |||||||
| Dynamic stability | ±5% in 10 msec. | |||||||
| Voltage distortion | <1% with linear load / ≤3% with non-linear load | |||||||
| Crest factor [lpeack/irms] | 3:1 | |||||||
| Frequency stability on battery | 0,05% | |||||||
| Frequency [Hz] | 50 or 60 (selectable) | |||||||
| Overload | 110% for 60 min; 125% for 10 min; 150% for 1 min. | |||||||
| BATTERIES | Â | |||||||
| Type | VRLA AGM / GEL; NiCd; SuperCaps; Li-ion; Flywheels | |||||||
| Residual ripple voltage | <1% | |||||||
| Recharge voltage compensation | -0,11% x V x °C | |||||||
| Typical charge current | 0,2 x C10 | |||||||
| OVERALL SPECIFICATIONS | Â | |||||||
| Weight without batteries [kg] | 200 | 220 | 230 | 255 | 302 | 416 | 616 | 665 |
| Dimensions (WxDxH) [mm] | 555x740x1400 | 800x740x1400 | 800x800x1900 | |||||
| Remote signals | dry contacts | |||||||
| Remote controls | ESD and bypass | |||||||
| Communications | Double RS232 + dry contacts + 2 slots for communications interface | |||||||
| Ambient temperature for the UPS | 0 °C - +40 °C | |||||||
| Recommended temperature for battery life | +20 °C - +25 °C | |||||||
| Range of relative humidity | 5-95% non-condensing | |||||||
| Colour | Dark grey RAL 7016 | |||||||
| Noise level at 1 m (ECO Mode) [dBA] | 60 | 62 | ||||||
| IP rating | IP20 | |||||||
| ECO Mode efficiency | up to 98% | |||||||
| Standards | European directives: LV 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111 | |||||||
| Classification in accordance with IEC 62040-3 | (Voltage Frequency Independent) VFI - SS - 111 | |||||||
| Moving the UPS | Pallet jack | |||||||
1Â For wider tolerance conditions apply.
BATAlso available with internal batteries.
| MODELS | MPT 10BAT | MPT 15BAT | MPT 20BAT | MPT 30 | MPT 40 | MPT 60 | MPT 80 |
|---|---|---|---|---|---|---|---|
| INPUT | Â | ||||||
| Rated Voltage [V] | 380 / 400 / 415 three-phase + N | ||||||
| Voltage tolerance [V] | 400 ±20% - 25% @ full load1 | ||||||
| Frequency [Hz] | 45-65 | ||||||
| Soft start | 0 - 100% in 120 sec. (selectable) | ||||||
| Permitted frequency tolerance | ±2% (selectable from ±1% to ±5% from front panel) | ||||||
| Standard equipment provided | Back Feed protection; separable bypass line | ||||||
| BYPASS | Â | ||||||
| Rated Voltage [V] | 380 / 400 / 415 three-phase + N | ||||||
| Rated frequency [Hz] | 50 or 60 (selectable) | ||||||
| OUTPUT | Â | ||||||
| Nominal power [kVA] | 10 | 15 | 20 | 30 | 40 | 60 | 80 |
| Active power [kW] | 9 | 13,5 | 18 | 27 | 36 | 54 | 72 |
| Number of phases | 3 + N | ||||||
| Rated voltage [V] | 380 / 400 / 415 three-phase + N (selectable) | ||||||
| Static stability | ±1% | ||||||
| Dynamic stability | ±5% in 10 msec. | ||||||
| Voltage distortion | <1% with linear load / ≤3% with non-linear load | ||||||
| Crest factor [lpeack/irms] | 3:1 | ||||||
| Frequency stability on battery | 0,05% | ||||||
| Frequency [Hz] | 50 or 60 (selectable) | ||||||
| Overload | 110% for 60 min; 125% for 10 min; 150% for 1 min. | ||||||
| BATTERIES | Â | ||||||
| Type | VRLA AGM / GEL; NiCd; SuperCaps; Li-ion; Flywheels | ||||||
| Residual ripple voltage | <1% | ||||||
| Recharge voltage compensation | -0,11% x V x °C | ||||||
| Typical charge current | 0,2 x C10 | ||||||
| OVERALL SPECIFICATIONS | Â | ||||||
| Weight without batteries [kg] | 228 | 241 | 256 | 315 | 335 | 460 | 520 |
| Dimensions (WxDxH) [mm] | 555x740x1400 | 800x740x1400 | |||||
| Remote signals | dry contacts | ||||||
| Remote controls | ESD and bypass | ||||||
| Communications | Double RS232 + dry contacts + 2 slots for communications interface | ||||||
| Ambient temperature for the UPS | 0 °C - +40 °C | ||||||
| Recommended temperature for battery life | +20 °C - +25 °C | ||||||
| Range of relative humidity | 5-95% non-condensing | ||||||
| Colour | Dark grey RAL 7016 | ||||||
| Noise level at 1 m (ECO Mode) [dBA] | 60 | 62 | |||||
| IP rating | IP20 | ||||||
| ECO Mode efficiency | up to 98% | ||||||
| Standards | European directives: LV 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111 | ||||||
| Classification in accordance with IEC 62040-3 | (Voltage Frequency Independent) VFI - SS - 111 | ||||||
| Moving the UPS | Pallet jack | ||||||
1Â For wider tolerance conditions apply.
BATAlso available with internal batteries.
| MODELS | MPT 100 | MPT 120 | MPT 160 | MPT 200 |
|---|---|---|---|---|
| INPUT | Â | |||
| Rated Voltage [V] | 380 / 400 / 415 three-phase | |||
| Voltage tolerance [V] | 400 ±20% - 25% @ full load1 | |||
| Frequency [Hz] | 45-65 | |||
| Soft start | 0 - 100% in 120 sec. (selectable) | |||
| Permitted frequency tolerance | ±2% (selectable from ±1% to ±5% from front panel) | |||
| Standard equipment provided | Back Feed protection; separable bypass line | |||
| BYPASS | Â | |||
| Rated Voltage [V] | 380 / 400 / 415 three-phase + N | |||
| Rated frequency [Hz] | 50 or 60 (selectable) | |||
| OUTPUT | Â | |||
| Nominal power [kVA] | 100 | 120 | 160 | 200 |
| Active power [kW] | 90 | 108 | 144 | 180 |
| Number of phases | 3 + N | |||
| Rated voltage [V] | 380 / 400 / 415 three-phase + N (selectable) | |||
| Static stability | ±1% | |||
| Dynamic stability | ±5% in 10 msec. | |||
| Voltage distortion | <1% with linear load / ≤3% with non-linear load | |||
| Crest factor [lpeack/irms] | 3:1 | |||
| Frequency stability on battery | 0,05% | |||
| Frequency [Hz] | 50 or 60 (selectable) | |||
| Overload | 110% for 60 min; 125% for 10 min; 150% for 1 min. | |||
| BATTERIES | Â | |||
| Type | VRLA AGM / GEL; NiCd; SuperCaps; Li-ion; Flywheels | |||
| Residual ripple voltage | <1% | |||
| Recharge voltage compensation | -0,11% x V x °C | |||
| Typical charge current | 0,2 x C10 | |||
| OVERALL SPECIFICATIONS | Â | |||
| Weight without batteries [kg] | 620 | 640 | 700 | 800 |
| Dimensions (WxDxH) [mm] | 800x800x1900 | |||
| Remote signals | dry contacts | |||
| Remote controls | ESD and bypass | |||
| Communications | Double RS232 + dry contacts + 2 slots for communications interface | |||
| Ambient temperature for the UPS | 0 °C - +40 °C | |||
| Recommended temperature for battery life | +20 °C - +25 °C | |||
| Range of relative humidity | 5-95% non-condensing | |||
| Colour | Dark grey RAL 7016 | |||
| Noise level at 1 m (ECO Mode) [dBA] | 65 | 68 | ||
| IP rating | IP20 | |||
| ECO Mode efficiency | up to 98% | |||
| Standards | European directives: LV 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111 | |||
| Classification in accordance with IEC 62040-3 | (Voltage Frequency Independent) VFI - SS - 111 | |||
| Moving the UPS | Pallet jack | |||
1Â For wider tolerance conditions apply.
BATAlso available with internal batteries.